describe metrics formula with cavets description
coldbox_performance_factor
Computes coldbox performance where value above 1 is alerting.
Computed only if any tower is active:
coldbox_performance_factor = 83 * PDT603 / ((PT603 + 14.7) * (TE504 + 459))
83
is correction factor14.7
is standard atm pressure base level459
is conversion for https://en.wikipedia.org/wiki/Rankine_scale